Combined Synopsis/Solicitation
Eaton Powerware System Replacement
Department of Veterans Affairs
SDVOSB set-aside · Manchester, NH
AI summary Beta
This summary may miss requirements: 2 of 5 attachments weren't read (Attachment A - Eaton 93E UPS manufacturer cut sheets and site electrical drawings Start-Up.pdf, Attachment B - Wage Determination No 2015-4019 rev 35.pdf). Check the attachments on SAM.gov.
Only service-disabled veteran-owned small businesses (SDVOSBs) can bid on solicitation 36C24127Q0030 from the Department of Veterans Affairs. The VA Medical Center in Manchester, New Hampshire wants its old Eaton Powerware 9390 uninterruptible power supply (UPS: a backup power unit) replaced with an Eaton 93E (or equal), plus maintenance for a base year and four option years. The response due date is November 30, 2026, 5:00 PM Eastern, by email; earlier versions gave November 26, 2026.
Who can bid (5)
- Must be a service-disabled veteran-owned small business; the certificate asks you to confirm you are verified in the Small Business Administration (SBA) VetCert database From 36C24127Q0030.docx
- Contractor must be qualified and authorized to work on Eaton products and have access to Eaton proprietary software From 36C24127Q0030.docx
- Signed limitations on subcontracting certificate: no more than 50% of the amount paid (excluding materials) to subcontractors that are not similarly situated entities From 36C24127Q0030.docx
Show all 5Show fewer
- Active SAM.gov registration when the quote is submitted From 36C24127Q0030.docx
- Licensed journeyman tradespeople; qualification and certification information for proposed employees and subcontractors goes in the quote From 36C24127Q0030.docx
How to submit: Email to Shawn.Lawrence@va.gov. What to include is under Full summary below. Check the solicitation's instructions on SAM.gov.
Things to watch (9)
From the version posted Nov 18, 2026.
- Serious: Only SDVOSBs can bid. This is a 100% set-aside; a business that is not a verified service-disabled veteran-owned small business cannot win. From 36C24127Q0030.docx
- Serious: Must be authorized to work on Eaton equipment. Bidders need manufacturer qualification and access to Eaton proprietary software, which a business without an Eaton relationship may not be able to get. From 36C24127Q0030.docx
- Serious: Signed subcontracting certificate required with quote. The VA will not evaluate or award without the certificate, and at most 50% of the money may go to firms that are not similarly situated entities. From 36C24127Q0030.docx
Show all 9Show fewer
- Worth checking: Stand-by hours do not add up. The work statement describes twice-yearly shutdowns of 12 hours each, but also says to provide 48 hours; ask the contracting officer how to price it. From 36C24127Q0030.docx
- Worth checking: Routine parts are inside your base price. The contractor supplies all parts for preventive maintenance at its own cost, including replacement batteries as needed, so price that risk in. From 36C24127Q0030.docx
- Worth checking: Four-hour emergency response and 24-hour repairs. Emergency call-backs need a response within four hours, and repairs are due within 24 hours after the need is found. From 36C24127Q0030.docx
- Minor: Parts limit differs by line. Parts are set at $2,500 NTE per year, while the work statement describes $500 per equipment item per visit with a cost proposal within 24 hours above that. From 36C24127Q0030.docx
- Minor: Service Contract Act wage rates apply. Wage Determination 2015-4019, Revision 35 (Hillsborough County, NH) sets minimum pay for the workers; the file is attached but was not read here. From 36C24127Q0030.docx
- Minor: The site visit was Nov 12, 2026. Check the notice and its amendments for whether attendance was required, and whether another visit is offered.
Read from the notice and 3 attachments. 2 of 5 not read. Show which files.
- 36C24127Q0030_2.docx (read)
- 36C24127Q0030_1.docx (read)
- 36C24127Q0030.docx (read)
- Attachment A - Eaton 93E UPS manufacturer cut sheets and site electrical drawings Start-Up.pdf: not summarized: open it on SAM.gov
- Attachment B - Wage Determination No 2015-4019 rev 35.pdf: not summarized: open it on SAM.gov
Full summary
What they want
- Replace the existing Eaton Powerware 9390 UPS with an Eaton 93E UPS and Extended Battery Cabinet, or equal (CLIN 0005, QTY 1 JOB; a contract line item number (CLIN) is one priced line of the order)
- Basic Eaton training course for staff on the new UPS (CLIN 0006, QTY 1 JOB)
- Quarterly and annual preventive maintenance and inspections of the UPS and its batteries (CLIN X001, QTY 4 QTR per year)
- Stand-by labor for large electrical shutdowns twice a year (CLIN X002, QTY 48 HR per year)
- Emergency on-call repair labor with a response within four (4) hours (CLIN X003, QTY 32 HR per year)
- Parts for non-routine repairs under a Government-set not-to-exceed (NTE) amount of $2,500 per year (CLIN X004, QTY 1 YR)
- A written report within one week of each maintenance activity, a yearly maintenance calendar and safety plans, including lock-out/tag-out (locking equipment off while it is worked on)
- Contract type
- Request for quotation (RFQ); firm-fixed-price (FFP: one set price, whatever the work ends up costing) line items, with Government-set not-to-exceed parts lines
- Period of performance
- Base Year: January 4, 2027 through January 3, 2028, plus four (4) option years (successive 12-month periods, if exercised). The notice also includes FAR 52.217-9, Option to Extend the Term of the Contract.
- Place of performance
- VA Medical Center, Manchester, 718 Smyth Road, Manchester, NH 03104
- Estimated value
- Not stated
- How they'll choose
- Best value: the Government will award to the responsible bidder whose quote is most advantageous, price and other factors considered
- Offers due
- November 30, 2026, 5:00 PM Eastern
- How to submit
- Email to Shawn.Lawrence@va.gov
What they'll judge offers on
- Technical or Quality: how well the quote meets or exceeds the Government's requirements in the Statement of Work
- Past Performance: relative risk of success based on the bidder's record, such as the contracting officer's knowledge, customer surveys, past performance questionnaire replies or the Contractor Performance Assessment Reporting System (CPARS)
- Price: total of all line-item prices, including all options; offers with significantly unbalanced option prices may be found unacceptable
What to include when you submit
- Include the solicitation number, your name, address, telephone number and Unique Entity Identifier (UEI)
- Put unit and extended prices on every line item for the base year and all four option years
- On the parts and materials lines (CLIN X004), carry the $2,500 NTE amount shown; do not price it competitively
- Include information needed to evaluate technical quality, past performance and price
- Include qualification and certification information for the proposed employees and subcontractors
- Include a statement of how far you agree with the solicitation's terms
- Include one of the two terms and conditions statements: acceptable without change, or acceptable with listed exceptions and reasons
- Return the signed and completed VAAR 852.219-75 certificate of compliance (limitations on subcontracting) with the quote
- Return the completed 852.240-70 (Compliance with Public Law 119-37, Section 258) form with the quote
- Hold prices firm for 60 calendar days after the date offers are due
- Complete representations and certifications in SAM.gov (the federal contractor database)
Not in the notice text
- Attachment A (Eaton 93E cut sheets, site and electrical drawings, start-up scope of work) and Attachment B (wage determination) are attached but not read; the replacement UPS details and wage rates are in them
- The technical information to send with the quote is said to be in Section 7, which is not in the documents read
- The 852.240-70 form is called Attachment C in the clause list and the 852.219-75 certificate Attachment E; only the 852.219-75 text was in the files read (labeled Attachment C)
- The full text of 852.204-72, called Attachment D, was not among the files read
- The Government's estimated value is not given
- How long the extension under FAR 52.217-9 can run is not stated in the text read
More to check before you bid
- Not certified through VetCert yet? Apply on VetCert (SBA), or start with the SDVOSB guide. More open service-disabled veteran-owned set-asides under NAICS 811310
Notice details
Notice type, codes, versions and files
- Posted
- Nov 18, 2026
- Notice type
- Combined Synopsis/Solicitation
- Office
- 241-Network Contract Office 01 (36C241), Togus, ME
- Product/service code
- J061 · Maint/Repair/Rebuild of Equipment – Electric Wire and Power Distribution Equipment
- Business type
- Equipment repair & maintenance (FedReady's grouping, from NAICS 811310)
- Versions
3 versions have been posted, newest first.
- Nov 18, 2026 · Amendment 0002 (this version)Due Nov 30, 2026 (changed)
- Nov 10, 2026 · Amendment 0001Due Nov 26, 2026
- Nov 4, 2026 · Combined Synopsis/SolicitationDue Nov 26, 2026
- Attachments
Before you respond
- How to respond to a solicitation (8 steps)
- How to read a government solicitation
- How to price a government contract
- Open SDVOSB set-aside contracts
Terms on this notice: Solicitation, SDVOSB (service-disabled veteran-owned small business), Set-aside