Solicitation
Halon Bottle Inspection
Department of Defense · Department of the Army
Small business set-aside · FL
A newer version of this notice was posted Nov 20, 2026. See the latest version.
AI summary Beta
Summary of the version posted Nov 19, 2026. The notice was amended Nov 20, 2026. Check what else changed on SAM.gov. The notice looks incomplete: Only the PWS was attached, so the submission instructions, evaluation factors, price schedule and contract clauses aren't in the text read; check the solicitation on SAM.gov. Check the attachments on SAM.gov.
Only small businesses can bid on solicitation W50S6Y27RA002, a total small business set-aside, and the performance work statement (PWS, the job description) also requires an Amerex distributor with a USDOT RIN. The Army (for the 125 Florida Air National Guard) wants 33 Amerex model 600K 150-lb halon fire bottles given their 12-year hydrostatic (water pressure) test, dip tube inspection and new O-rings, on base in Florida. The work takes 2 to 3 business days. The response due date is November 27, 2026, 12:00 PM Eastern.
Who can bid (5)
- Total small business set-aside: only small businesses can bid From SAM.gov's set-aside field
- Must be an Amerex distributor with manufacturer training and certifications for working on Model 600 wheeled fire extinguishers From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
- Hold a valid USDOT RIN number (a U.S. Department of Transportation registration for testing pressure cylinders) From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
Show all 5Show fewer
- Have a closed recovery transfer and reclaim system and proper training for transferring halocarbons From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
- At least 5 years of company experience working on Amerex model 600 flightline extinguishers From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
Things to watch (6)
- Serious: Total small business set-aside. Only small businesses can bid; larger firms cannot send an offer.
- Serious: Must be an Amerex distributor. The PWS requires an Amerex distributor with manufacturer training for Model 600 extinguishers, which most small businesses are not and cannot become by writing an offer. From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
- Serious: USDOT RIN number and halocarbon reclaim equipment required. You need a valid USDOT RIN and a closed recovery transfer and reclaim system with trained staff to handle the halon. From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
Show all 6Show fewer
- Worth checking: Five years of Amerex model 600 experience. The PWS asks for at least five years of company experience on this exact model, which narrows the field. From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
- Worth checking: Base access and background checks. Workers need base passes and background checks that the PWS says may take multiple weeks, and gate closures are not paid. From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
- Minor: Work window of 2 to 3 business days, 6:30 AM to 5:00 PM weekdays. All 33 bottles must be done inside that short on-base window, outside holidays and base closures. From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf
Read from the notice and 1 attachment. Show which files.
- I.A.02. PWS and PRS MXG Halon Bottle KO.pdf (read)
Full summary
What they want
- Do the one-time 12-year hydrostatic test (pressure test) on QTY 33 each Amerex model 600K 150-lb halon fire bottles, to National Fire Protection Association (NFPA) 10 standards
- Pressure test both the cylinder and the discharge hose assembly of each bottle
- Inspect the inside of each cylinder's dip tube for wear, corrosion, cracking or deterioration
- Remove old discharge hose O-rings and install new compatible ones; rebuild valves with new valve stems and O-rings on each bottle
- Supply the nitrogen for repressurizing, leak checking and system prep, plus all labor, tooling and shop supplies
- Build and keep a spreadsheet of every serial number and the type of maintenance done
- Send a quality control plan (QCP) to the Contracting Officer no later than 10 days after contract award
- Give paperwork showing all 33 bottles are inspected (the performance standard is 100%)
- Period of performance
- 2 to 3 business days
- Place of performance
- 125 Florida Air National Guard, in the Alert area (the PWS refers to a map attachment); Florida
- Remote work
- No. From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf:
The Government does not permit the contractor to telework in support of this requirement.
- Estimated value
- Not stated
- Offers due
- November 27, 2026, 12:00 PM Eastern (from the version posted Nov 19, 2026; amended since)
After award, you must have
- Base access: background checks and base identification for every worker, and Antiterrorism Level I training within 15 calendar days after the contract start date From I.A.02. PWS and PRS MXG Halon Bottle KO.pdf:
…shall complete AT Level I training within 15…
Not in the notice text
- Only the PWS was attached, so the submission instructions, evaluation factors, price schedule and contract clauses aren't in the text read; check the solicitation on SAM.gov
- How and when to prove the Amerex distributor, USDOT RIN and halocarbon reclaim certifications isn't stated
- Paragraph 3.0 (Government-furnished items) is referred to but isn't in the text, and the map of the Alert area is not included
- The street address of the work site isn't given, only 125 Florida Air National Guard and the Alert area
- The Government's estimated value isn't stated
- Contract type isn't stated
More to check before you bid
- Service contracts usually set minimum pay rates (the Service Contract Act). Price the labor with the SCA price calculator.
Notice details
Notice type, codes, versions and files
- Posted
- Nov 19, 2026
- Notice type
- Solicitation
- Office
- W7M2 Uspfo Activity Flang 125, Jacksonville, FL
- Product/service code
- J042 · Maint/Repair/Rebuild of Equip – Fire Fighting/Rescue/Safety Equip; Environ Protect Equip/Matls
- Business type
- Equipment repair & maintenance (FedReady's grouping, from NAICS 811310)
- Versions
6 versions have been posted, newest first.
- Nov 20, 2026 · Amendment 0003Due Nov 27, 2026
- Nov 19, 2026 · Amendment 0002 (this version)Due Nov 27, 2026
- Nov 19, 2026 · Amendment 0001Due Nov 27, 2026
- Nov 19, 2026 · SolicitationDue Nov 27, 2026 (changed)
- Nov 7, 2026 · Amendment 0001Due Nov 13, 2026 (changed)
- Nov 7, 2026 · Sources SoughtDue Jul 13, 2027
- Attachments
Before you respond
- How to respond to a solicitation (8 steps)
- How to read a government solicitation
- How to price a government contract
- Set-aside contracts explained
Terms on this notice: Solicitation, Set-aside
Full notice text from SAM.gov
Similar open opportunities
- Fire Extinguisher Inspection, Maintenance, Recharge, Repair, Hydrostatic TestingOpen to all businesses (no set-aside), solicitation W5S09H27QA991 asks for a single 5-year blanket purchase agreement (BPA: a standing deal where the buyer orders as needed…
- Inspection, maintenance and repair of cryogenic storage tanks.The Navy's Fleet Readiness Center East at MCAS Cherry Point, NC wants a contractor to inspect and maintain four cryogenic (super-cold liquid gas) storage tanks twice a year, plus…
- CTX VAMC Maintenance, Calibration, Inspection, and Testing of the Electrical Power Distribution SystemSolicitation 36C25727Q0089: only service-disabled veteran-owned small businesses (SDVOSBs) listed in VA's Vendor Information Pages (VIP) can bid.
- Maintenance, Repair, and Inspection of Hoists in the Kaiserslautern Military Community (KMC)The U.S. Air Force (786 CES, Ramstein Air Base, Germany) wants a contractor to maintain, repair and inspect the real-property hoists and cranes across the Kaiserslautern Military…